SUNCOURT® RADON FAN MODEL: RDN04 & RDN04-3, RDK04 & RDK04-3 INSTALLATION INSTRUCTIONS READ THESE INSTRUCTIONS BEFORE PLANNING YOUR INSTALLATION PLEASE READ AND SAVE THESE INSTRUCTIONS: DO NOT CONNECT POWER SUPPLY UNTIL FAN IS COMPLETELY INSTALLED. CAUTION: BEFORE CARRYING OUT ANY MAINTENANCE OR SERVICING, ENSURE THE UNIT IS DISCONNECTED FROM THE MAIN POWER SUPPLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE NEVER EXPOSE THIS FAN TO TEMPERATURES EXCEEDING 140°F (60°C). WARNING - TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. Do not use fan in hazardous environments where the fan electrical system could provide ignition to
(1) Running watts at zero static pressure FAN SPECIFICATIONS Electric Motor • External Rotor • Ball Bearing • Class B • Thermally Protected • Conforms To ANSI-UL 705 & CSA 22.2 • ETL Listed • Housing Material FRABS • UV Protected • Flame Rating UL 94V0 • Housing Color White
INSTALLATION Retain original packaging.
MOUNTING Mount the fan vertically with the outlet up. Insure the unit is plumb and level. When mounting directly to the system piping ensure that the fan does not contact any building surface to avoid vibration noise. Use the flexible couplers provided to secure the fan to the piping. MOUNTING BRACKET The fan may be further secured with the mounting brackets provided. The flexible couplings will provide means of disconnect for cleaning the impeller and also to isolate vibration.
ELECTRICAL WIRING The fans operate on standard 120V 60 Hz AC. All wiring must be performed in accordance with the National Electrical Code and state and local building codes. A qualified electrician should perform all ELECTRICAL CONNECTION Connect wiring with terminal block provided, observing proper connections.
CONDENSATION & DRAINAGE Condensation can form in the piping of a mitigation system when the air in the piping is chilled below its dew point. This can occur at points where the system piping goes through unheated space such as an attic, garage or outside. The system design must provide a means for water to drain back to a slab hole to remove the condensation. The fan MUST be mounted vertically plumb and level, with the outlet pointing up for proper drainage through the fan. Avoid mounting the fans in any orientation that will allow water to accumulate inside the fan housing. The fans are NOT suitable for underground burial. Under some circumstances a condensate bypass should be installed in the outlet ducting as shown in Figure 1. This may be particularly true in cold climate installations, which require long lengths of outlet ducting or when the outlet ducting is likely to produce large amounts of condensation because of high soil moisture or outlet duct material. Schedule 20 piping and other thin-walled plastic ducting or
The bypass is constructed with a 45 degree Wye fitting at the bottom of the outlet stack. The bottom of the Wye is capped and fitted with a tube that connects to the inlet piping or other drain. The condensation produced in the outlet stack is collected in the Wye fitting and drained through the bypass tube. The bypass tubing may be insulated to prevent freezing. Failure to install a proper condensate collection system voids the product warranty. MAINTENANCE Inspect the product at least once every 12 months for excessive dust and dirt build up on the impeller (more often in dusty environments). Clean as necessary. The unit must be disconnected from power during inspection and/or cleaning. “SYSTEM ON” INDICATOR Install a “system on” indicator to confirm status. A pressure indicator, manometer, or vacuum alarm is recommended for this purpose. The Suncourt Air Pressure Indicator is included with models RDK04 and RDK04-3. SLAB COVERAGE The Suncourt Radon Fan provides coverage up to 2000 sq. ft. per slab penetration depending on type of sub slab material. If one slab penetration does not sufficiently mitigate the Radon then additional slab penetration points can be added as required. Detailed Radon information is available on the EPA’s website at: http://www.epa.gov/radon/ FIVE YEAR LIMITED WARRANTY Subject to the following limitations, Suncourt Inc. (manufacturer) warrants that the fan will, for 5 (five) years from date of original purchase, remain free from appearance of defects in workmanship or materials. This warranty is subject to the following limitations: (a) manufacturer’s liability is limited to the replacement or repair of the unit, as decided by the manufacturer; (b) a defective unit must be returned, prepaid, with proof of purchase, to Suncourt; and (c) this warranty does not apply to defects resulting from the alteration, abuse, accidental damage, unauthorized repair, or misuse of the unit. This warranty is given in lieu of all other warranties, guarantees, and conditions on manufacturer’s part, and the manufacturer shall have no tortious or other liability in respect to this fan. There is no implied warranty of merchantability and fitness for a particular purpose. Suncourt shall not be liable for any direct, indirect, special, incidental or consequential damages arising from, or relating to, the fan or the performance of it. Suncourt’s maximum liability shall not exceed the amount of the purchase price of the fan. The sole remedy under this warranty shall be the repair or replacement of the product. WARRANTY RETURN Call Suncourt at 1.800.999.3267 for a Return Goods Authorization (RGA) number. Please have date of original purchase available. Mark the RGA number clearly on the return shipping box. We do not accept returns without a valid RGA number. Package the unit using the original packaging including the styrofoam inserts to avoid damage in shipping. SUNCOURT INC.
|
|
![]() |
|